Power and Power Factor

  • In a purely resistive AC circuit, the energy delivered by the source will be dissipated as heat by the resistor.
  • In a purely capacitive or purely inductive circuit, all of the energy will be stored during a half cycle, and then returned to the source during the other --- there will be no net conversion to heat.
  • When there is both a resistive component and a reactive component, some energy will be stored, and some will be converted to heat during each cycle.

Power Equations

Purely Resistive Circuit

Suppose a circuit with load RR resistance is supplied a voltage of v(t)=Vmcos⁡ωtv(t)=V_m\cos{\omega t}.

Instantaneous power dissipated by the load is given by:

p(t)=Vm2Rcos⁡2(ωt)p(t) = \frac{V_m^2}{R}\cos^2{(\omega t)}

Always: p(t)>0p(t)\gt 0.

Average power=12×Peak power=Vm22R\text{Average power} = \frac{1}{2}\times\text{Peak power}=\cfrac{V_m^2}{2R}

Purely Inductive Circuit

Suppose a circuit with inductor LL is supplied a voltage of v(t)=Vmcos⁡ωtv(t)=V_m\cos{\omega t}.

Instantaneous power dissipated by the load is given by:

p(t)=Vm22ωLsin⁡(2ωt)p(t) = \frac{V_m^2}{2\omega L}\sin{(2\omega t)}

The inductive reactive power is given by:

Q=V2ωL=I2ωLQ = \frac{V^2}{\omega L} = I^2 \omega L

Purely Capacitive Circuit

Suppose a circuit with capacitor CC is supplied a voltage of v(t)=Vmcos⁡ωtv(t)=V_m\cos{\omega t}.

Instantaneous power dissipated by the load is given by:

p(t)=−Vm2ωC2sin⁡(2ωt)p(t) = -\frac{V_m^2 \omega C}{2}\sin{(2\omega t)}

The capacitive reactive power is given by:

Q=V2ωC=I2ωLQ = V^2\omega C = \frac{I^2}{\omega L}

General Load

Consider a general load with both resistive and reactive components. Depending on how inductive or capacitive the reactive component, the phase shift between voltage and current phasor lies between 90°90° and −90°-90°.

Suppose the circuit is supplied a voltage of v(t)=Vmcos⁡(ωt)v(t) = V_m\cos{(\omega t)}. And the current phasor shifts in θ\theta phase angle.

i(t)=Imcos⁡(ωt−θ)i(t) = I_m\cos{(\omega t - \theta)}

This ends up with:

p(t)=12VmIm[cos⁡θ+cos⁡(2ωt−θ)]p(t) = \frac{1}{2}V_mI_m\bigg[\cos\theta+\cos (2\omega t - \theta)\bigg]

Average over 1 Cycle

Pavg=1T∫t0t0+Tp(t) dt=VrmsIrmscos⁡θP_\text{avg} =\frac{1}{T}\int_{t_0}^{t_0 + T} p(t)\,\text{d}t = V_{\text{rms}}I_{\text{rms}}\cos{\theta}

Types of Power

Active Power

Also known as true power, resistive power. In all electrical and electronic systems, it is the true power (the resistive power) that does the work.

P=VrmsIrmscos⁡θP = V_{\text{rms}}I_{\text{rms}}\cos{\theta}

Reactive Power

Power delivered to/from a pure energy storage element (inductors and capacitors) is known as reactive power.

  • Average power consumed by a pure energy storage element is 00.
  • Current associated with it is not 00. Transmission lines, transformers, fuses, etc. must all be designed to withstand this current.
  • Loads with energy storage elements will draw large currents and require heavy duty wiring even though little average power is consumed.
  • Shuttles back and forth between the source and the load.
Qreactive=VrmsIrmssin⁡θQ_\text{reactive} = V_\text{rms}I_\text{rms}\sin\theta

Apparent Power

Combination of active and reactive power.

S=VrmsIrms=P2+Q2S = V_\text{rms}I_\text{rms} = \sqrt{P^2 + Q^2}

The apparent power is essentially the effective power that the source “sees”.

The Beer Analogy

  • Beer - Active power
    Liquid beer is useful power. The power that does the work.
  • Foam - Reactive power
    Wasted or lost power.
  • Mug - Apparent power
    Demand power, that is being delivered by the utility.

Power Factor

If θ\theta is the phase angle difference between vv and ii, cos⁡(θ)\cos(\theta) is called the power factor. Higher power factor indicates a more efficient use of electrical power.

Power factor appears in the equation of PavgP_\text{avg}.

cos⁡θ=Active powerApparent power=ResistanceImpedance\cos{\theta} =\frac{\text{Active power}}{\text{Apparent power}} =\frac{\text{Resistance}}{\text{Impedance}}

Power factor is:

  • leading when II leads VV
  • lagging when II lags VV

Power Triangle

A right triangle that visually represents the relationship between active, reactive and apparent power in an AC circuit.

They are represented as below:

  • Active Power (P)
    On the horizontal axis
  • Reactive Power (Q)
    On the vertical axis
  • Apparent Power (S)
    On the hypotenuse of the triangle
S2=P2+Q2S^2 = P^2 + Q^2

The angle θ\theta between the active power and the apparent power represents the phase angle, and the cosine of this angle is the power factor:

cos⁡θ=PS\cos{\theta} = \frac{P}{S}
Written by October 17, 2026 3 min read